product

Power Range : 1000 – 3000 VA

The TERRA RT inverter model is equipped with innovative features:

  • On-line double conversion
  • 3-level battery charger (high-performance chargers) to optimize battery life and efficiency
  • Extended autonomy by using additional battery cabinets
  • Large tolerance range for input voltage in order to avoid using the batteries and preserving autonomy
  • Input power factor: 0.99
  • Returns higher than 90% in online mode

Advantages

  • Multi-function LCD display
  • High power factor and low THDI
  • ECO function option to increase returns
  • Power generator compatible
  • Possibility of putting up to 4 ASI in parallel
  • Joint or separate possibility for parallel system
  • Configurable number of batteries
  • Automatic battery test configuration
  • Multi-branch battery configuration
  • Different communication systems
  • Battery start
  • Emergency stop function

GENERAL FEATURESTERRA RT - 1TERRA RT - 2TERRA RT - 3
Power rating (KVA/KW)1000 / 9002000 / 18003000 / 2700
Power rating (KVA/KW)On-line double conversion
INPUT FEATURES
Voltage200/208/220/230/240 Vac (1P + N)
Frequency45 à 65 Hz Auto-detection
Voltage range110-160 Vac charged up to 30% and 160-200 Vac charged up to 80%

200-290 Vac charged at 100%
Power factor> 0,98
TDHI< 7 to 100% with non-linear charge
Connection1 IEC320 C14-10A Plug1 IEC320 C20-16A Plug
OUTPUT FEATURES
Voltage200/208/220/230/240 Vac (1P + N)
Frequency50 or 60 Hz
Crest factor3 :1
Voltage regulation+/- 2%
THDu≤ 3% with linear charge / ≤ 5 to 100% with non-linear charge
Return (in online mode)90% in online mode
Connection6 IEC320 C13-10A Plugs6 IEC320 C13-10A Plugs

1 IEC320 C19-16A Plug
STATIC BY-PASS
TypeAutomatic bypass
Voltage rangeStandard (+15% / -45%) Configurable (+5%, +10%, +25%) / (-20%, -30%) Frequency ± 10%
COMMUNICATION AND DISPLAY
DisplayLCD for indicating measurements

Lights for indicating operational status
Emergency stop switchAvailable
Communication portsRS 232 / USB
ENVIRONMENT
Operating temperature0° to 25°C
Noncondensing relative humidity0 to 90%
Sound level 1 meter away< 55 dB
CERTIFICATIONS
Standards and markingsCE- IEC 62040-1- IEC 62040-2-IEC 60950-1
OPTIONS
CommunicationSNMP card and dry relay contacts card
AccessoriesRail kit for 19'' rack mount
MAINTENANCE BY-PASS
TypeOption: External maintenance bypass
UPS DIMENSIONS
H x L x P (in mm)440 x 86.5 (2U) x 430440 x 86.5 (2U) x 572440 x 86.5 (2U) x 696
Weight (en kgi15.1

22.225.5
EXTERNAL BATTERY CABINET
Dimensions (H x L x P in mm)440 X 86.5 (2U) x 430440 x 86.5 (2U) x 572440 x 86.5 (2U) x 696
Weight with battery (in kg)122232
Battery typeBatterie plomb étanche sans entretien Technologie VRLA
Recharge time5 heures
Recharge current1.4 A max
AUTONOMY
In mn 9

Autonomy: Upon consultation.

Note: Non-contractual document. The technical specifications mentioned in this document are subject to change without notice from us.