Central power systems

product

Presentation

Legislation requires for the installation of security lighting with an autonomy of at least six hours in Establishments that are open to the public (shops, hotels, cinemas, theatres, amphitheatres, conference rooms…).

The central power system is part of the most secure solutions which guarantees and ensures people’s safety, but also the operation and maintenance of installations.

This equipment is held to regulated operating standards and to periodic verification requirements.

We offer a large range of central power systems for alternative or continual security which meets NF C 71 815 and NF EN 50 171 standards. In line with the legislation for public places.

What is a lighting central power system?

  • They are easy to maintain
  • Easy to use
  • The evacuation lighting points ensure visibility from afar (constantly switched on)

 

We carry out the following services:

  • They are easy to maintain
  • Easy to use
  • The evacuation lighting points ensure visibility from afar (constantly switched on)

Suivis de vos équipements via nos contrats de maintenance

  • Functional equipment verification
  • Drafting a technical report
  • Maintenance
  • Verifying the contractual battery life over one hour
  • Recording the visit in the security logbook

In order to guarantee the proper functioning of your equipment.
For any request, please contact us.

Central power systems

Mesure de la tension secteur 1

Tension secteur 1U1.NSeuil miniSeuil maxi 
U ms232.1 V206 V264 VEn tolérance
Fréquence50Hz45Hz65HzEn tolérance
Taux de distorsion TcH-f2.06 %5 %En tolérance
Taux de distorsion TcH-ms2.07 %5 %
CirconstancesUps on
Commentaire

Mesure de la tension ASI

Tension ASIU1.NSeuil miniSeuil maxi 
U ms236.4 V222 V237 VEn tolérance
Fréquence49.91Hz49.5Hz50.5HzEn tolérance
Taux de distorsion TcH-f6.95 %5 %Hors tolérance
Taux de distorsion TcH-ms6.95 %5 %
CirconstancesUPS en charge
Commentaire